Input
Operating Voltage Ranges:
Model 120AZ: 0 to 132 VAC 50/60 Hz
Model 240AZ: 0 to 264 VAC 50/60 Hz
Max. Power Consumtion:
Model 120AZ: 2.6VA @132 VAC
Model 240AZ: 4.5VA @264 VAC Control
Adjustment: On-board trimpot
Undervoltage Setpoint Range:
Model 120AZ: 78 - 99 VAC
Model 240AZ: 156 - 199 VAC
Reset Point Voltage:
Model 120AZ: 104 VAC
Model 240AZ: 209 VAC
Repeatability:
±0.5% for fixed conditions
±1% over temperature range
Voltage Sense Accuracy: ±2% @25°C
Power Off Reset Time: 150 mS max.
Output
Type: Relay Contacts, S.P.D.T. (1 form C) Silver Cad. Oxide material
Rating: 8 Amp.max. resistive at 250 VAC & 30 VDC; 100 mA at 5 VDC minimum load
current
Indication: Green LED; ON for normal condition |
Protection
Transient Voltage: 30 joule Metal Oxide Varistor
Dielectric breakdown:
3000 Vrms terminal to mounting
1500 Vrms input to output.
Insulation resistance:
100 megohms min. between terminals and case Mechanical
Termination: .25 x.032 male fast-on terminals
Mounting: Surface mount with one #8 screw
Life:
10,000,000 cycles min. mechanical
100,000 cycles min electrical
Environmental
Storage Temperature: -40°C to 85°C
Operating Temperature: -23°C to 55°C
Humidity: 95% relative max. |