Time Delay
Adjustment: 3 digit pushbutton switch
Range: 50 mS to 999 hours in 6 ranges
Repeatability: ± 0.1% of set time or ± 20 mS whichever is greater.
Accuracies: All Functions . . ± 1% of set time or ± 20 mS whichever is greater.
Input
- Operating Voltage:
- 24 - 240VAC ± 15%, 50/60 Hz;
- 24 - 240VDC ± 15%, (DC Unfiltered input voltage
must be full-wave rectified)
- Power On Response: 50 mS max.
- Power Off Reset Time: Requires power
interruption of 150mS max. (50 mS typ.)
- Start Switch Closure Time: 50 mS. min. to
initiate timing cycle; 50 mS. min.to reset delay during timing cycle
- Power Consumption:
- 14 VA max. at 276 VAC,
- 2.5 VA max.at 24 VAC
Output
- Type: Relay D.P.D.T. (2 form C) Silver Cad.
Oxide material
- Rating: 10 amp. max. resistive at 240 VAC,
125VDC 1/2 HP at 240 VAC 10 mA at 5 VDC min. Load current
- Life:
- Mechanical - 10,000,000 operations
- Full Load - 500,000 operations
Environmental
Storage Temperature: -25°C to 70°C
Operating Temperature: -25° to 55°C
Humidity: 95% relative
Mechanical
Termination: 11-pin plug or spade type
Mounting:
Back Panel Mounting: Spade Base use MSO-00KUP-012 11 Pin Base use MSO-0011P-012
Front Panel Mounting: (1.78" sq. opening required)
Front Panel Mounting Bracket MBK-1/16D-011 11 Pin Base use MSO-0011P-013 |
Protection
Transient Voltage: 30 joule, 250 volt metal oxide varistor
Dielectric Breakdown: 1800 VAC, RMS minimum at 60 Hz between input and outputs and
between outputsTiming Light Logic
Repeat Cycle: Full On during "Off" time; Flashing during "On"
time
Other Logic Modes: Flashing during timing; Full On after time out
Timing
Selectable Time Ranges:
.05 to 9.99 seconds
.1 to 99.9 seconds
1 to 999 seconds
.1 to 99.9 minutes
1 to 999 minutes
1 to 999 hours
(Times less than 50 mS are not recommended due to the response time of the mechanical
relay)
Selectable Operating Logic Modes: Repeat
Cycle (50% fixed duty cycle)
Single Shot (1 shot)
Delay On Break (D.O.B.)
Interval (Intervl)
Delay On Make (D.O.M.)
Programming:
To program the timer, remove voltage from the unit and select the operating logic mode and
the time range; use the digital switches to select the required time (0-999)
Note: 1) Do not apply voltage or ground to the
Start switch, 2) Switch leads should be shielded when running close to other wires (Start
switch supplied by customer) |