Delay On Break -
Retriggerable
Time Delay Relays
T3 Series
Voltage is
applied to the timer at all times. Upon a closure of a normally open isolated start
switch, the output relay is activated and remains so as long as the switch is kept closed.
When the start switch is opened, timing starts. At the end of the preset time delay, the
output relay is de-activated and the timer is ready for a new cycle.
Note: 1) Do not apply voltage or ground to the
start switch; 2) Switch leads should be shielded when running close to other wires; 3) If
the start switch is reclosed during timing, the timer will reset and will not start timing
until Start switch is opened.
File #E59090
Digital Timing Circuit
±1% Repeatability
Superior transient Protection
Internal Components Supported By Heavy-duty Chassis
Flame-Retardant Polycarbonate Housing
100% Life Tested
Time Delays To 1 Hour
No False Contact Transfer When Reset During Timing
Fiberglass Reinforced Circuit Board
Reinforced Locator Pin
Made in U.S.A.
Time Delay
Adjustment: Knob, factory fixed on special order (Minimum order required)
Range: 50 mS to 1 hour in 11 ranges
Repeatability: ±1% at constant temperature
Accuracy: Maximum time -0%, +10%
Minimum
time +0%. -50%
Reset Time: 400 milliseconds maximum
Start Switch Closure Time: 20 mS to initiate timing; 50 mS to reset delay during
timing
Input
Operating Voltage: 24, 120 VAC; 12, 24 VDC ±10% (D.C. models have reverse polarity
protection. Unfiltered input voltage to them must be full-wave rectified)
Power Consumption: 3 VA maximum
Frequency: 50/60 Hz
Output
Type: Relay Contacts, S.P.D.T. (1 form C) or D.P.D.T. (2 form C) Silver Cad. Oxide
material
Rating: 10 amp. max. resistive at 240 volts A.C.; 100 mA at 5 VDC min. Load current
Life: Mechanical -10,000,000 operations
Full Load - 500,000 operations