The Model DNC-T2300-I/O module provides several functions. It
communicates with a T2310
or T2320 Dust Collector Timer via the RS-232 port to form an
Enhanced Timer system, and it communicates pertinent system data to
remote control/display devices via the 2 wire Enhanced Timer Network. It
also incorporates three 4-20mA current loop inputs, three contact
closure type inputs, and one "J" type thermocouple input. In
addition, the I/O board provides 16K bytes of non-volatile memory for
the storage of up to one year of input trending data. The I/O board
requires either a T2310 or T2320 Timer to program and operate the board
and a T2300 Display Panel to access data trending reports.
The I/O board offers significant versatility to the "Intelligent
Dust Collector Controller" system. It can monitor, display, alert,
and store dust collector system parameters from pressure sensors,
emission monitors, plenum air flow sensors, broken bag detectors, fan
motor current sensors and any other device which has a 4-20 mA current
output or contact closure output. The unit works in conjunction with the
T2310 & T2320 Timers and also with the DNC-T2300-DSP
Display Panel.
Operating Logic:Upon application of power to the unit,
communication will be established with the T2310 or T2320 Timer via the
RS-232 port. The I/O board can then be configured for the inputs
provided to it by using the keypad on the controller. Alarm setpoints
and 4 - 20 mA scaling can be programmed for different types of inputs to
be displayed in a meaningful fashion on the controller's 8 character
display and output via the two wire Enhanced Timer Network to the
DNC-T2300-DSP remote display panel.
Inputs: There are three general purpose 4-20mA current loop
inputs which are configured by the Timer. Depending on how the
particular 4-20 mA inputs are configured, the messages that appear on
the Timer's display would either show a generic range of 0-100% based on
the 4-20 mA input or data units specific to three pre-programmed sensing
devices would be displayed.
There are two general purpose switched inputs which will monitor and
report up to two contact closures as alarm conditions to the Timer, and
one contact closure input which allows the user to place the Enhanced
Timer system in standby mode.
The controller will display the temperature of the "J" type
thermocouple in degrees F, with a range of -40 deg. F to 700 deg. F
.
History Trending: The I/O board has the capability to store
data generated by the Timer connected to its RS-232 port as well as data
generated by the various sensing devices connected to its inputs. Data
history is subdivided into three categories: Short term history, Long
term history, and Alarm history. Short term history is a time and date
stamped recording of the hourly averages of the 4-20mA inputs, the
Differential Pressure from the Timer, the highest temperature recorded,
and the number of outputs that were pulsed in that hour. This Short term
history period is two weeks, after which time the oldest 24 hours of
recorded data is averaged along with the highest recorded temperature
and the number of outputs that were pulsed for that period and is stored
in Long term history. The Long term history period is one year, after
which time the oldest recorded data is discarded to make room for new
data. Alarm history is event driven, if any alarm conditions occur, a
time and date stamped "snapshot" of all the system parameters
is recorded in a First-In-First-Out circular data buffer. This FIFO
buffer can store up to 212 alarm events and is not time dependent. In
order to generate the Data History Reports, a DNC-T2300-DSP Remote
Display Panel and a terminal device capable of communicating standard
ASCII via an RS-232 connection are required.
Enhances T2310 & T2320 Operation
Monitors Three 4-20mA Analog Inputs
Monitors Three Switched Inputs
Operating Temperature Range from -40
deg. F to 150 deg. F
Communicates via RS232 Port to Intelligent Controller
Communicates via 2 wire Network to Remote Sites
Interconnectable for Overall System Management
Large Storage Capacity for Historical Trending of System Data
Aids in System Diagnostics
Use to Increase Overall System Efficiency
RTV Coating: Conformally coated for protection against vibration,
humidity and contamination
Metal Chassis Provided: For mounting directly into NEMA-4 Box
Timer Life Tested to eliminate field failures
File #E65038
One Year Warranty: Warranted to be free from defects in materials or
workmanship for One Year from date of purchase
Made in USA
Inputs:
Voltages:
105 -135 VAC, 50/60 Hz.
210 - 270 VAC, 50/60 Hz
4 - 20 mA Current Loops:
Input Impedance: 401.5 ohms +\- 20 ohms Accuracy:
+/- 1% of applied signal.
#1: Emissions/Aux1 (Sink Capability Only)
User Selectable Functions:
Emissions - Output is Percent of full scale input.
Generic - Output is Percent of full scale input.
#2: Air Flow/Aux2 (Sink Capability Only)
User Selectable Functions:
Air Flow - Pitot Tube sensing device required,
Output range: 0 to 6.5 Mega SCFM
Generic - Output is Percent of full scale input.
#3: Manifold/Aux3(Source or Sink Capability
Source Voltage: +24v +/- 2v
User Selectable Functions:
Manifold pressure - Output range: 0 to 999 PSI
Generic - Output is Percent of full scale input.
Switched Inputs:
Alarm Input Open Circuit Voltage: 40 VDC
Alarm Input Short Circuit Current: 4.5 mA
#1: Airlock Fault/Aux4 Alarm
Input will be labled and recorded as either
"Air Flow" or "Aux4" depending
on user selection.
#2: High Hopper/Aux5 Alarm
Input will be labled and recorded as either
"High Hopper" or "Aux5"
depending on user
selection.
#3: Standby
Function: Dedicated as a Remote Standby
Switch Input.
Thermocouple Input:
Thermocouple: Type "J"
Temp. Measurement Range: -40 to 700°F
Temp. Measurement Accuracy: ± 4°
F.
Serial Communications:
Null Modem type connection required between
Controller and I/O board.
Type: RS-232.
Mode: 4800 Baud, 8-Data Bits, 1-Start Bit, 1-Stop Bit, X ON -
X OFF, No Parity
Function: Dedicated For Communication with a T2300 Series
Dust Collector Controller.
Connector: Type 9-Pin Male IBM Compatible D-SUB Connector.
Null Modem type connection required between Controller and I/O
board.
Network Connection:
Type: 2 Wire Twisted Pair
Termination: 52.3 ohm, 1%, 1/8 watt resistor
Network Connection Device: FTT-10A Transceiver
Environmental:
Operating Temperature Range:
-40° to 150°F, -40°
to 65° C
Humidity: 90% Non-Condensing
Environmental Protection: RTV Conformal Coating for Humidity
and Vibration