Time Delay
Adjustment: Knob or external resistor, factory fixed on special order (Minimum
order required)
Range: 50 mS to 10 hours in 16 ranges
Repeatability: ± 1% at constant temperature
Accuracy: Maximum time -0%, +10%;
Minimum
time +0%, -50%
Reset Time: 50 mS maximum (25 mS typical)
Input
Operating Voltage: 24, 120, 240 VAC; 12, 24 VDC ± 10% (D.C. models have reverse
polarity protection. Unfiltered input voltage to them must be full-wave rectified)
Power Consumption: 3 VA maximum
Frequency: 50/60 Hz
Output
Type: Relay Contacts, D.P.D.T. (2 form C)
Silver Cad. Oxide
material
Rating: 10 amp. max. resistive at 240 volts A.C.;
100
mA at 5 VDC min. load current
Life: Mechanical -10,000,000 operations
Full Load - 500,000 operations |
Protection
Transient Voltage: 12, 24 volt timers are protected by an 8.8 joule metal oxide
varistor; 120, 240 volt timers are protected by a 30 joule metal oxide varistor
Dielectric Breakdown: 1500 VAC, RMS minimum at 60 Hz between input and outputs and
between outputs
Mechanical
Termination: 8-pin or 11-pin plug
Mounting:
Socket Mount- 8-Pin Part Number MSO-0008P-012
Socket Mount- 11-Pin Part Number MSO-0011P-012
Environmental
Storage Temperature: -23°C to 70°C
Operating Temperature: -23° to 55°C |