Intelligent, AC-Input, Pulse Cleaning of Bag House Dust Collectors
Models DNC-T2310 and DNC-T2320

TM100
DNC-T2320 Shown
 

Models T2310 & T2320 are microprocessor based bag house filter controllers which combine a ten or twenty output sequencer with a solid state differential pressure sensor to form a small size, and low cost replacement to the separate solid state sequencer and pressure gauge combination most often used in on demand pulse jet cleaning systems. These controllers will sense the pressure difference across the filters of a bag house and initiate a cleaning cycle when the filters start to impede the air flow. When the pressure drops to normal the controller will stop cycling.
 
Operating Logic
Standard Timer Operation Status Indication: The Timer can show the following information on its 8 character alpha-numeric display during normal operation: · DP from 0" to 15" water column · High or Low DP Alarms · Solenoid Fault Conditions · Current Output being Pulsed · Auxiliary Alarm Input Closures Upon occurance of any alarm event, the alarm status is reported on the display along with the output number that was pulsed during the time of the event.

Standard Operating Logic The controllers can operate in the following modes:

  • Auto Output
    Only configured outputs will be pulsed
    Output faults will be detected and indicated
  • Manual Output
    Outputs will recycle after last output used
  • Single Cycle Output
    Single cycle cleaning can be initiated by keypress regardless of pressure input
  • Continuous Cycle
    Controller will cycle indefinitely when the Pressure Bypass/Cycle Down Input is shorted
  • Cycle Down
    The outputs will be pulsed through a user seleced number of complete cycles when the Bypass/Cycle Down Input is shorted. This cycle will occur regardless of pressure input.
  • Expanded Output Mode
    Controller will cycle to output #10 or #20, then will initiate an extended output mode via the Alarm Input and Output terminals to NCC's DNC-T2000 Series Dust Collector Controllers. This will facilitate systems which require greater than 10 or 20 outputs.
  • Alarm Outputs
    The isolated Alarm Output contacts will close for alarm conditions such as output faults, high pressure alarm, warm-up failure, etc. During an alarm condition, a corresponding message is displayed
  • Alarm Input
    A closure across the Alarm Input terminals will be indicated on the display as well as initiate the Alarm Output

In addition to the standard operation of the T2310 & T2320, an enhanced operation option is available with the use of the DNC-T2300-I/O Remote Input/Output module in conjunction with the DNC-T2300-DSP Remote Annunciator Panel. The T2310 & T2320 Timers along with the DNC-T2300-I/O constitutes the "Enhanced Timer" system which allows the user to monitor and record the data parameters associated with a dust collector system. This system can range in size from 1 to 255 dust collectors, all reporting to a central location, the DNC-T2300-DSP.

Enhanced Timer Operation Status Indication: The Timer can show the following information on its 8 character alpha-numeric display during normal operation: · DP from 0" to 15" water column · High or Low DP Alarms · Solenoid Fault Conditions · Current Output being Pulsed · Auxiliary Alarm Input Closures · DNC-T2300-I/O Analog Input Status · DNC-T2300-I/O Alarm Input Closures Upon occurance of any alarm event, the alarm status is reported on the display along with the output number that was pulsed during the time of the event.
RS-232 Port:

  • Remote Terminal
    An ANSI type terminal is required for remote monitoring and programming of the controller. Connection to the controller is made via the RS-232 port (9 pin D-Sub connector). All the functions and display status accessible from the controller is available through the ANSI terminal.
  • Remote I/O Interface
    The 2310/2320 controllers are capable of communication with the DNC-T2300-I/O board via the RS-232 port. This allows the user to monitor up to three 4-20mA analog inputs, three contact closure type inputs, and one J type thermocouple. The I/O module is programmed via the 2310/2320 keypad and can be user defined to set alarm points from remote sensors of parameters such as emission, air flow, pressure, broken bags, fan motor current, etc. Refer to the data sheet for the DNC-T2300-I/O for additional information.


Programming Logic: The controller as supplied from the factory will require user configuration. Upon application of power the display will indicate "SETUP". The operator must then configure the various operating parameters using the six key keyboard of the controller before normal cleaning operation can begin. The programmable parameters for Standard Operation as displayed are:

  • OUTPUT
    Auto Configuration - will automatically sense the solenoids connected to the outputs and will only pulse those outputs during cleaning cycles.
    Manual Configuration - the controller will pulse each output until the last output programmed and then recycle to output #1
  • LAST - the number of the last output used.
  • LO P - Low Pressure Setpoint, the pressure at which the controller will stop its cleaning cycle.
  • HI P - High Pressure Setpoint, the pressure at which the controller will start its cleaning cycle.
  • ON - Output Solenoid On Time.
  • OFF - Off Delay Time Between Output Solenoid Activation.
  • ALARM - High Differential Pressure Alarm Set-Point, the pressure at which the controller will close its alarm contacts

For Enhanced Timer programming information, see IDC Programming Tree on PDF Catalog page.


Additional Features:The 2310/2320 controllers also provide:

  • 4 - 20 Milliampre Output Loop
    This output will provide a continuous reading from 4 -20 mA corresponding to the sensed differential pressure range of 0" to 15" water column.This is a standard feature.
  • 24 Hour Time / Day / Month Clock The clock feature will allow a daily automatic turn on and turn off command to be implemented by the controller. It can be programmed to start and stop the cleaning cycles for up to seven events per week. This is an optional feature found on the "B" series models
Features
  • On-Board Differential Pressure Sensor
  • 4 - 20 mA Output for DP
  • 8 Character Alphanumeric Display
  • Microprocessor Based Control for Stable Timing from -40° F to 150°F
  • Enhanced Timer Option:
     ›· Monitor Additional Devices
     ›· Record Dust Collector Data
     ›· Network Timers Together
     ›· Remote Network Monitor
     ›· Remote Network Control
  • RS232 Port for Remote Monitor & Control
  • Automatic Output Setup Capability
  • High Pressure Alarm Indication
  • Expanded Cycle Mode allows additional Dust Collector controllers to expand output capabilites
  • Output Fault Detection
  • Alarm Output Contacts
  • Alarm Input Sensors
  • Pulse Time: Line synchronized to eliminate 8 milliseconds triac turn off variation per Output
  • 10 Amp 400V Output Triacs for maximum protection against output shorts. 200VA load rating
  • RTV Coating: Conformally coated for protection against vibration, humidity and contamination
  • Metal Chassis Provided: For mounting directly into NEMA-4 Box
  • Timer Life Tested for 24 Hours: To eliminate field failures
  • Input protection: 30 joule metal oxide varistor
  • UR File #E65038
  • One Year Warranty: Warranted to be free from defects in materials or workmanship for One Year from date of purchase
  • Made in USA
Specifications
Factory Default Settings:
  Lo Pressure = 2" water column
  HI Pressure = 4" water column
  Alarm Pressure = 14" water column
  Output Quantity = 10 or 20
  Off Time = 15 seconds
  On Time = 0.10 seconds
  Output Configuration = Manual
  I/O Expansion = No

Inputs:
Voltage: 105 -135 VAC, 50/60 Hz.
      210 - 270 VAC, 50/60 Hz
Maximum Ratings at 135 VAC Input Voltage:
  Power Consumtion: 10 VA, without loads
  •DNC-T2310:
  Bypass Switch Open Circuit Voltage: 24 VDC.
  Bypass Switch Short Circuit Current: 4.3m
  Alarm Inputs 1-3:
        Open Circuit Voltage: 24VDC.
        Short Circuit Current: 4.3 mA
  •DNC-T2320:
  Bypass Switch Open Circuit Voltage: 24 VDC.
  Bypass Switch Short Circuit Current: 4.3mA
  Alarm Inputs 1-3:
        Open Circuit Voltage: 24VDC.
        Short Circuit Current: 4.3 mA
  Auxiliary Input #4: 90-135 VAC, 50/60 Hz
                                    6.6mA at 135 VAC

Air Pressure Measurement:
Sensor Type: Silicon Piezoresistive Transducer with Dual Inlets
Measurement Range: 0.0 to 15.0 Inches of Water
Accuracy: ± 2% of Full Scale at 77° Fahrenheit / 25° Celsius ± 6% of Full Scale Over Temperature and Voltage Range
Maximum Continuous Pressure: 10 PSI.

Display:
Type: 8 Character 16 Segment Vacuum Fluorescent Display; Characters: .2" High, Alpha-Numeric
Timing:
Solenoid On Time Range: .01 - .50 Seconds.
Solenoid Off Time Range: 1 -180 Seconds.
Timing Accuracy: -2 mS, +10 mS or ±1%, whichever is greater. Solenoid On Time is synchronized to the AC Line.

Outputs:
Maximum Solenoid Output: 200VA or Watts at maximum duty cycle.
Solenoid Output Voltage: Input Voltage - 2.5 VAC @ 200 VA Load
Solenoid Output Type: Solid State TRIAC.
Solenoid Output Short Circuit Protection: 3AG Fast Acting 3A/250 VAC Fuse.
• DNC-T2310:
  Alarm Output Type:
      1-FORM A Relay Contact.
  Alarm Output Rating:
      3 Amp @ 120/240 VAC
• DNC-T2320:
  Alarm Output Type:
      1-FORM A Relay Contact
  Alarm Output Rating:
      3 Amp @ 120/240 VAC
  Aux. Output #4 Type:
      1-FORM A Relay Contact
  Aux. Output #4 Rating:
      3 Amp @ 120/240 VAC
Current Loop:
 Type: 4 - 20 mA current loop, current is sourced by the controller. Signal represents 0 - 15 inches of differential pressure (DP). Accuracy: ±.3 mA of displayed pressure.

Serial Communications:
Type: RS-232.
Terminal Emulation: ANSI VT100
Mode: 9600 Baud, 8-Data Bits, 1-Start Bit, 1-Stop Bit, X ON - X OFF, No Parity
Connector: Type 9-Pin Male IBM Compatible D-SUB Connector

Environmental:
Operating Temperature Range:-40° to 150° Fahrenheit, -40° to 65° Celsius
Environmental Protection: Conformal Coating for Humidity and Vibration