Intelligent, AC-Input, Pulse Cleaning of Bag House
Dust Collectors
Models DNC-T2310 and DNC-T2320
DNC-T2320 Shown
Models T2310 & T2320 are
microprocessor based bag house filter controllers which combine a ten or twenty output
sequencer with a solid state differential pressure sensor to form a small size, and low
cost replacement to the separate solid state sequencer and pressure gauge combination most
often used in on demand pulse jet cleaning systems. These controllers will sense the
pressure difference across the filters of a bag house and initiate a cleaning cycle when
the filters start to impede the air flow. When the pressure drops to normal the controller
will stop cycling.
Standard Timer Operation Status Indication:
The Timer can show the following information on its 8 character alpha-numeric display
during normal operation: · DP from 0" to 15" water column · High or Low DP
Alarms · Solenoid Fault Conditions · Current Output being Pulsed · Auxiliary Alarm
Input Closures Upon occurance of any alarm event, the alarm status is reported on the
display along with the output number that was pulsed during the time of the event.
Standard Operating Logic The controllers can operate in the following modes:
Auto Output
Only configured outputs will be pulsed
Output faults will be detected and indicated
Manual Output
Outputs will recycle after last output used
Single Cycle Output
Single cycle cleaning can be initiated by keypress regardless of pressure input
Continuous Cycle
Controller will cycle indefinitely when the Pressure Bypass/Cycle Down Input is shorted
Cycle Down
The outputs will be pulsed through a user seleced number of complete cycles when the
Bypass/Cycle Down Input is shorted. This cycle will occur regardless of pressure input.
Expanded Output Mode
Controller will cycle to output #10 or #20, then will initiate an extended output mode via
the Alarm Input and Output terminals to NCC's DNC-T2000 Series Dust Collector Controllers.
This will facilitate systems which require greater than 10 or 20 outputs.
Alarm Outputs
The isolated Alarm Output contacts will close for alarm conditions such as output faults,
high pressure alarm, warm-up failure, etc. During an alarm condition, a corresponding
message is displayed
Alarm Input
A closure across the Alarm Input terminals will be indicated on the display as well as
initiate the Alarm Output
In addition to the standard operation of the T2310 & T2320, an enhanced
operation option is available with the use of the DNC-T2300-I/O Remote Input/Output module
in conjunction with the DNC-T2300-DSP Remote Annunciator Panel. The T2310 & T2320
Timers along with the DNC-T2300-I/O constitutes the "Enhanced Timer" system
which allows the user to monitor and record the data parameters associated with a dust
collector system. This system can range in size from 1 to 255 dust collectors, all
reporting to a central location, the DNC-T2300-DSP.
Enhanced Timer Operation Status Indication: The Timer can show the following
information on its 8 character alpha-numeric display during normal operation: · DP from
0" to 15" water column · High or Low DP Alarms · Solenoid Fault Conditions ·
Current Output being Pulsed · Auxiliary Alarm Input Closures · DNC-T2300-I/O Analog
Input Status · DNC-T2300-I/O Alarm Input Closures Upon occurance of any alarm event, the
alarm status is reported on the display along with the output number that was pulsed
during the time of the event.
RS-232 Port:
Remote Terminal
An ANSI type terminal is required for remote monitoring and programming of the controller.
Connection to the controller is made via the RS-232 port (9 pin D-Sub connector). All the
functions and display status accessible from the controller is available through the ANSI
terminal.
Remote I/O Interface
The 2310/2320 controllers are capable of communication with the DNC-T2300-I/O board via
the RS-232 port. This allows the user to monitor up to three 4-20mA analog inputs, three
contact closure type inputs, and one J type thermocouple. The I/O module is programmed via
the 2310/2320 keypad and can be user defined to set alarm points from remote sensors of
parameters such as emission, air flow, pressure, broken bags, fan motor current, etc.
Refer to the data sheet for the DNC-T2300-I/O for additional information.
Programming Logic: The controller as supplied from the factory will require user
configuration. Upon application of power the display will indicate "SETUP". The
operator must then configure the various operating parameters using the six key keyboard
of the controller before normal cleaning operation can begin. The programmable parameters
for Standard Operation as displayed are:
OUTPUT
Auto Configuration - will automatically sense the solenoids connected to the
outputs and will only pulse those outputs during cleaning cycles.
Manual Configuration - the controller will pulse each output until the last output
programmed and then recycle to output #1
LAST - the number of the last output used.
LO P - Low Pressure Setpoint, the pressure at which the
controller will stop its cleaning cycle.
HI P - High Pressure Setpoint, the pressure at which the
controller will start its cleaning cycle.
ON - Output Solenoid On Time.
OFF - Off Delay Time Between Output Solenoid
Activation.
ALARM - High Differential Pressure Alarm Set-Point,
the pressure at which the controller will close its alarm contacts
For Enhanced Timer programming information, see IDC
Programming Tree on PDF Catalog page.
Additional Features:The 2310/2320 controllers also provide:
4 - 20 Milliampre Output Loop
This output will provide a continuous reading from 4 -20 mA corresponding to the sensed
differential pressure range of 0" to 15" water column.This is a standard
feature.
24 Hour Time / Day / Month Clock The clock feature
will allow a daily automatic turn on and turn off command to be implemented by the
controller. It can be programmed to start and stop the cleaning cycles for up to seven
events per week. This is an optional feature found on the "B" series models
On-Board Differential Pressure Sensor
4 - 20 mA Output for DP
8 Character Alphanumeric Display
Microprocessor Based Control for Stable Timing from
-40° F to 150°F
Enhanced Timer Option:
· Monitor Additional Devices
· Record Dust Collector Data
· Network Timers Together
· Remote Network Monitor
· Remote Network Control
Pulse Time: Line synchronized to eliminate 8
milliseconds triac turn off variation per Output
10 Amp 400V Output Triacs for maximum protection
against output shorts. 200VA load rating
RTV Coating: Conformally coated for protection
against vibration, humidity and contamination
Metal Chassis Provided: For mounting directly into
NEMA-4 Box
Timer Life Tested for 24 Hours: To eliminate field
failures
Input protection: 30 joule metal oxide varistor
File #E65038
One Year Warranty: Warranted to be free from defects
in materials or workmanship for One Year from date of purchase
Made in USA
Factory Default
Settings:
Lo Pressure = 2" water column
HI Pressure = 4" water column
Alarm Pressure = 14" water column
Output Quantity = 10 or 20
Off Time = 15 seconds
On Time = 0.10 seconds
Output Configuration = Manual
I/O Expansion = No
Inputs:
Voltage: 105 -135 VAC, 50/60 Hz.
210 - 270 VAC, 50/60 Hz
Maximum Ratings at 135 VAC Input Voltage:
Power Consumtion: 10 VA, without loads
DNC-T2310:
Bypass Switch Open Circuit Voltage: 24 VDC.
Bypass Switch Short Circuit Current: 4.3m
Alarm Inputs 1-3:
Open Circuit Voltage: 24VDC.
Short Circuit Current: 4.3 mA
DNC-T2320:
Bypass Switch Open Circuit Voltage: 24 VDC.
Bypass Switch Short Circuit Current: 4.3mA
Alarm Inputs 1-3:
Open Circuit Voltage: 24VDC.
Short Circuit Current: 4.3 mA
Auxiliary Input #4: 90-135 VAC, 50/60 Hz
6.6mA
at 135 VAC
Air Pressure Measurement:
Sensor Type: Silicon Piezoresistive Transducer with Dual Inlets
Measurement Range: 0.0 to 15.0 Inches of Water
Accuracy: ± 2% of Full Scale at 77° Fahrenheit / 25°
Celsius ± 6% of Full Scale Over Temperature and Voltage Range
Maximum Continuous Pressure: 10 PSI.
Timing:
Solenoid On Time Range: .01 - .50 Seconds.
Solenoid Off Time Range: 1 -180 Seconds.
Timing Accuracy: -2 mS, +10 mS or ±1%, whichever is greater. Solenoid On
Time is synchronized to the AC Line.
Outputs:
Maximum Solenoid Output: 200VA or Watts at maximum duty cycle.
Solenoid Output Voltage: Input Voltage - 2.5 VAC @ 200 VA Load
Solenoid Output Type: Solid State TRIAC.
Solenoid Output Short Circuit Protection: 3AG Fast Acting 3A/250 VAC Fuse.
DNC-T2310:
Alarm Output Type:
1-FORM A Relay Contact.
Alarm Output Rating:
3 Amp @ 120/240 VAC
DNC-T2320:
Alarm Output Type:
1-FORM A Relay Contact
Alarm Output Rating:
3 Amp @ 120/240 VAC
Aux. Output #4 Type:
1-FORM A Relay Contact
Aux. Output #4 Rating:
3 Amp @ 120/240 VAC
Current Loop:
Type: 4 - 20 mA current loop, current is sourced by the controller. Signal
represents 0 - 15 inches of differential pressure (DP). Accuracy: ±.3 mA of displayed
pressure.
Serial Communications:
Type: RS-232.
Terminal Emulation: ANSI VT100
Mode: 9600 Baud, 8-Data Bits, 1-Start Bit, 1-Stop Bit, X ON - X OFF, No Parity
Connector: Type 9-Pin Male IBM Compatible D-SUB Connector
Environmental:
Operating Temperature Range:-40° to 150° Fahrenheit, -40° to 65° Celsius
Environmental Protection: Conformal Coating for Humidity and Vibration