Time Delay
Adjustment: 3-digit pushbutton switch
Range: 50 mS to 999 minutes in 5 ranges
Repeatability: ± 0.1%, ± 20 mS over specified timing range
Accuracy: ± 1% of set time, plus fixed error of 80 mS max. (40 mS typical
including power on response time)
Input
Operating Voltage: 24, 120, 240 VAC, 12, 24 VDC ± 10% (D.C. models have reverse
polarity protection. Unfiltered input voltage to them must be full-wave rectified)
Power On Response: 50 mS max.
Power Off Reset Time: 150 mS min.
Start Switch Closure Time: 200 mS to initiate timing cycle; 50 mS to reset delay
during cycle
Power Consumption: 2 VA maximum
Frequency: 50/60 Hz
Output
Type: Relay Contacts, D.P.D.T. (2 form C)
Silver Cad. Oxide
material
Rating: 10 amp. max. resistive at 240 volts A.C.
100 mA at 5 VDC min. load current
Life: Mechanical - 10,000,000 operations
Full Load - 500,000 operations
Timing Light Logic: Flashing during timing; continuously on after time out |
Protection
Transient Voltage: 12, 24 volt timers are protected by an 8.8 joule metal oxide
varistor; 120, 240 volt timers are protected by a 30 joule metal oxide varistor.
Dielectric Breakdown: 1500 VAC RMS minimum at 60 Hz between input and outputs and
between outputs.
Mechanical
Termination: 8 - pin plug
Mounting: Socket Mount - Part No. MSO-0008P-012
Environmental
Storage Temperature: -23°C to 70°C
Operating Temperature: -23°C to 55°C
Humidity: 95% relative
Timing
Selectable Time Ranges:
.05 to 9.99 seconds
.1 to 99.9 seconds
1 to 999 seconds
.1 to 99.9 minutes
1 to 999 minutes
(Times less than 50 mS are not recommended due to the response time of the mechanical
relay)
Programming:
To program the timer, remove power from the unit and select the time range, use the
digital switches to select the required time (0-999)
|