Fluke 430 Series
Three-Phase Power Quality Analyzers
Specifications
Product Home -
Features -
Specifications - Ordering Information -
Pricing
|
Technical Data |
| Inputs |
| Number: |
4 voltage and current (3 phases +
neutral) |
| Maximum voltage: |
1000 Vrms (6 kV peak) |
| Maximum sampling speed: |
200 kS/s on each channel simultaneously |
|
| Volt/Amps/Hertz |
| Vrms (AC + DC) |
|
| Measurement range: |
1 ... 1000 V |
| Accuracy: |
0.5% of Vnom |
|
|
| Vpeak |
|
| Measurement range: |
1 ... 1400 V |
| Accuracy: |
5% of Vnom |
|
|
| Crest factor |
|
| Measurement range: |
1.0 ... > 2.8 |
| Accuracy: |
±5% |
|
|
| Arms (AC + DC) |
|
| Measurement range: |
0 ... 20 kA |
| Accuracy: |
±1% ± 5 counts |
|
|
| Apeak |
|
| Measurement range: |
0 ... 5.5 kA |
| Accuracy: |
5% |
|
|
| Crest factor |
|
| Measurement range: |
1 ... 10 |
| Accuracy: |
±5% |
|
|
| Hz (60 Hz nominal) |
|
| Measurement range: |
51.00 ... 69.00 Hz |
| Accuracy: |
±1% ± 5 counts |
|
| Dips and swells |
| Vrms (AC+DC) ³ |
|
| Measurement range: |
0.0% … 100% of Vnom |
| Accuracy: |
±1% of Vnom |
|
|
| Arms (AC+DC) ³ |
|
| Measurement range: |
0 ... 20 kA |
| Accuracy: |
±1% ± 5 counts |
|
| Harmonics |
| Harmonic (interharmonic) (n) |
|
| Measurement range: |
DC, 1..50; (Off, 1..49) measured
relative to fundamental or to total rms |
|
|
| Vrms |
|
| Measurement range: |
0.0 … 1000 V |
| Accuracy: |
±5% ± 2 counts |
|
|
| Arms |
|
| Measurement range: |
0.0 … 4000 mV x clamp scaling |
| Accuracy: |
±5% ± 5 counts |
|
|
| Watts |
|
| Measurement range: |
Depends on clamp scaling |
| Accuracy: |
±5% ± n x 2% or reading, ± 10 counts |
|
|
| DC voltage |
|
| Measurement range: |
0.0 … 1000 V |
| Accuracy: |
±5% ± 10 counts |
|
|
| THD |
|
| Measurement range: |
0.0 … 100.0% |
| Accuracy: |
±2.5% |
|
|
| Hz |
|
| Measurement range: |
0 … 3500 Hz |
| Accuracy: |
± 1 Hz |
|
|
| Phase angle |
|
| Measurement range: |
-360º ... +360º |
| Accuracy: |
± n × 1.5º |
|
| Power and energy |
| Watt, VA, VAR |
|
| Measurement range: |
1.0 … 20.00 MVA¹ |
| Accuracy: |
±1.5% ± 10 counts |
|
|
| kWh, kVAh, kVARh |
|
| Measurement range: |
00.00 …200.0 GVAh¹ |
| Accuracy: |
± 1.5% ± 10 counts |
|
|
| Power Factor/ Cos Ф / DPF |
|
| Measurement range: |
0…1 |
| Accuracy: |
± 0.03 |
|
| Flicker |
| Pst (1 min), Pst, Plt, PF5 |
|
| Measurement range: |
0.00 … 20.00 |
| Accuracy: |
±5% |
|
| Unbalance |
| Volts |
|
| Measurement range: |
0.0 … 5.0% |
| Accuracy: |
±0.5% |
|
|
| Current |
|
| Measurement range: |
0.0 … 20% |
| Accuracy: |
± 1% |
|
| Transient Capture |
| Volts |
|
| Measurement range: |
±6000 V |
| Accuracy: |
±2.5% of Vrms |
| Minimum detect duration |
5 µs (200kS/s sampling) |
|
| Inrush mode |
| Arms (AC+DC) |
|
| Measurement range: |
0.000 … 20.00 kA¹ |
| Accuracy: |
±1% of meas ± 5 counts |
|
| Autotrend recording |
| Sampling: |
Up to 100 readings/s continuous
sampling per channel |
| Memory: |
Up to 3600 min, max and avg points for
each reading |
| Recording time: |
Up to 450 days |
| Zoom: |
Up to 12x horizontal zoom |
|
| Memory |
| Screens: |
Fluke 434 - 50; Fluke 433 - 25 |
| Data sets including recordings: |
Fluke 434 - 10; Fluke 433 - 5 |
|
| Notes |
¹ Depending on clamp scaling
² Value is measured over 1 cycle, commencing at a fundamental zero
crossing, and refreshed each half-cycle
|
The advanced functions Interharmonics, Energy, Transients and Inrush are
optional for the Fluke 434 and standard available on the Fluke 435.
|
Environmental Specifications |
| Operating temperature |
| |
0 ºC to +50 ºC (32 ºF to 122 ºF) |
|
|
Safety Specifications |
| Safety |
EN61010-1 (2nd edition) pollution degree 2; 1000 V CAT III / 600 V
CAT IV ANSI/ISA S82.01
|
|
Mechanical & General
Specifications |
| Size |
| |
256 x 169 x 64 mm (10 x 6.6 x 2.5 in) |
|
| Weight |
|
| Warranty |
|
| Battery life |
| Rechargeable NiMH pack: |
>7 hours |
| Charging time: |
4 hours typical |
|
| Shock & Vibration |
| |
Shock: 30g
Vibration: MiL-PRF-2880F Class 2 |
|
| Case |
| |
Rugged, shockproof with integrated protective holster, IP51 (dust, drip, waterproof) |
|
|