Fluke 1550 Megohmeter
Specifications
Product Home
- Features - Models, Options &
Accessories - Pricing
Electrical Specifications | Mechanical
Specifications | Power |
Environmental
Specifications
|
Software Specifications
Electrical
Specifications
Insulation
Resistance Measurement
Test Voltage
(dc)
Range
Accuracy
(± reading)
250 V
200 kΩ
to 5 GΩ
5 GΩ to 50 GΩ
5 %
20 %
500 V
200 kΩ
to 10 GΩ
10 GΩ to 100 GΩ
5 %
20 %
1000 V
200 kΩ
to 20 GΩ
20 GΩ to 200 GΩ
5 %
20 %
2500 V
200 kΩ
to 50 GΩ
50 GΩ to 500 GΩ
5 %
20 %
5000 V
200 kΩ
to 100 GΩ
100 GΩ to 1 TΩ W
5 %
20 %
Short
circuit current
Greater
than 1 mA and less than 2 mA
Bar
graph range
0
to 1 TΩ
Insulation
test voltage accuracy
-0
% to + 10 % at 1 mA load current
Induced
ac mains current rejection
2
mA maximum
Charging
rate for capacitive load
5
seconds per µF
Leakage
current
Range:
1 nA to 2 mA
Accuracy: ±(5 % + 2 nA)
Capacitance
measurement
Range:
0.01 µF t 15.00 µF
Accuracy: ± (15 % rdg + 0.03 µF)
Live
circuit Indicator
Range:
30 V to 600 V ac/dc, 50/60 Hz
Accuracy: ± (5 % + 2 V)
Timer
0
to 99 minutes; settable in 1 minute increments; indicated to within 1
second
Ramp
0
% to 100 % of selected test voltage, or until breakdown
The meter’s accuracy is specified for
one year after calibration at operating temperatures of 0 ºC to 35 ºC. For
operating temperatures outside the range (-20 ºC to 0 ºC and 35 ºC to 50 ºC),
add +/- .25 % per ºC, except on the 20 % bands add +/- 1 % per ºC.
Mechanical
Specifications
Dimensions
(L x W x H)
170
mm x 242 mm x 330 mm
(6.7 in x 9.5 in x 13.0 in)
Weight
(with battery)
4
kg (8.8 lbs)
Power
Battery
type
12
volt, lead-acid, rechargeable
Charger
input (AC)
85
to 250 V ac 50/60 Hz 50 VA
Battery
life (typical) Note: At higher temperatures, the battery requires more frequent charging.
Test voltage
Number of
tests
250 V
4138
500 V
3913
1 kV
3462
2.5 kV
2043
5 kV
1000
Environmental
Specifications
Operating
temperature
-20
°C to 50 °C (-4 °F to 122 °F)
Storage
temperature
-20
°C to 65 °C (-4 °F to 149 °F)
Relative
Humidity
80
% at 31 °C decreasing linearly to 50 % at 40 °C
Operating
altitude
0
to 2000 meters
Enclosure
sealing
IP-40
Shock,
vibration
MIL-PRF-28800F,
Class II
EMI
immunity
EN
61326
Safety
EN
61010-1, CAT III, 600 V,
EN61557, PARTS 1 & 2
Input
Overload Protection
600
V ac continuous
Software
Specifications
Quicklink
1550B Software
Requires
a PC running Windows® 95, 98, Me,
2000, NT4.0
Two-year warranty