Model
514
Catalog# 2117.70
Features | Applications
| Specifications
The
AEMC Clamp-on Meter Model 514 is a general purpose professional clamp-on
meter that measures up to the toughest standards. It is built into a
rugged mechanical case and is designed using quality polycarbonate
materials.This meter offers a complete set of measurement ranges and is
in compliance with international safety and quality standards to ensure a
professional and reliable measuring tool. The Model 514 is autoranging and
provides the best measurement range and resolution for troubleshooting. It
has a high resolution 40A range.
The Model 514 measures AC Amps, AC Volts, DC Volts, Ohms, Continuity (with
beeper), Frequency (from V or A) and has a Diode Test function. The Model
514 also uses Hall sensor technology that provides both DC and AC current
measurements to 1000A.
The Model 514 is sized for a comfortable, one-handed operation. This model
is average sensing and designed for traditional average responding
electrical systems.
Features
Standard size, full function
clamp-on meter
1000AAC current measurements
750VAC/1000VDC volt measurements
TRMS measurements
Resistance measurement to 4000Ω
Continuity with beeper below 40Ω
Frequency measurements from V
and A
Diode test
1ms Peak function for fast
capture of signals
Hold function to
"freeze" readings
Push-button for easy ADC zeroing
Large easy-to-read 4000-count
display
42-segment analog bargraph
Supplied with test leads and
soft carrying case
Applications
Commercial, industrial, residential
and HVAC troubleshooting
Power panel, junction box and battery
bank monitoring
AC or DC motor testing
Power plant troubleshooting
Electrical testing and troubleshooting
on non-linear loads, such as adjustable speed drives and computers
Electrical Specifications
AC Current
Range
0.05
to 1000Arms
Resolution
40A:
0.01A; 400A: 0.1A; 1000A: 1A
Basic Accuracy
50
to 60Hz: ±1.9% of Reading ± 5cts;
60 to 500Hz: ±2.5% of Reading + 5cts
Frequency Range
50
to 500Hz
Overload
Protection
1200
Arms
DC Amperes
Range
1A
to 1000A
Resolution
40A:
0.01A, 400A: 0.1A; 1000A: 1A
Accuracy
±2.5%
of Reading ± 10cts
Overload
Protection
1200
Arms
AC Volts
Input
Range
0.5V
to 750V
Resolution
400V:
0.1V
/ 750V: 1V
Accuracy
±1.5%
of Reading ± 5cts
Input
Impedance
10MΩ
Overload
Protection
1000Vrms
Frequency
Input
Current
Input
Voltage
Input
Range
4kHz
10kHz
4kHz
10kHz
Resolution
1Hz
10Hz
1Hz
10Hz
Minimum
Input Signal
2Arms
5Arms
5Vrms
10Vrms
Accuracy
±0.1%
of Reading ± 1ct
(20 to 10kHz)
±0.1%
of Reading ± 1ct
(10 to 10kHz)
DC Volts
Range
0.2
to 1000V
Resolution
400V:
0.1V; 1000V: 1V
Accuracy
±1%
of Reading ± 2cts
Input
Impedance
10MΩ
Overload
Protection
1000Vrms
Continuity
Range
Beeper
Measurement
<40Ω
Max.
Test Voltage
3VDC
Overload
Protection
600Vrms
General Specifications
Digital Display:
Digital: 3¾ digits LCD display,
4000-count (max. reading 3999)
Analog Display:
Fast 42-segment analog bargraph
display
Symbol & Scale Range:
Automatic according to range and
input signal
Polarity:
Minus sign displayed when
negative signal applied to input
Overload:
OL Displayed when input signal
exceeds range
Sample Rate:
2 samples/sec for the digital
display; 20 samples/sec for the analog bargraph
Jaw Opening Size:
1.575" (40mm)
Battery:
9V, NEDA 1604 or 6F22 or 006P
Low Battery Indicator:
Symbol displayed when the battery
is below the required voltage
Auto Power Off:
The meter will power itself OFF
if there is no push button or rotary switch operation for 30 minutes
Dimensions:
9.53 x 2.60 x 1.42" (242 x
66 x 36mm)
Weight:
14.10oz (400g) with batteries
Environmental
Specification
Operating
Temperature:
32° to 104°F (0°
to 40°C), <80% RH, non-condensing
Storage
Temperature:
14° to 140°F
(-10° to 60°C), <70% RH, battery removed
Operating
Altitude:
2167 ft (2000m)
Safety /
Reference Specifications
Protection
Level:
Double
insulation; EN 61010, 600V, Cat. III and EN 61010, 1000V,
Cat. II
Agency
Approvals:
CE Mark