Ground resistance, harmonics, insulation
and transformer Testing

AEMC Products  AEMC Pricing

Model 514
Catalog# 2117.70

Features | Applications | Specifications

AEMC Model 514 Clamp Meter

The AEMC Clamp-on Meter Model 514 is a general purpose professional clamp-on meter that measures up to the toughest standards. It is built into a rugged mechanical case and is designed using quality polycarbonate materials.

This meter offers a complete set of measurement ranges and is in compliance with international safety and quality standards to ensure a professional and reliable measuring tool. The Model 514 is autoranging and provides the best measurement range and resolution for troubleshooting. It has a high resolution 40A range.

The Model 514 measures AC Amps, AC Volts, DC Volts, Ohms, Continuity (with beeper), Frequency (from V or A) and has a Diode Test function. The Model 514 also uses Hall sensor technology that provides both DC and AC current measurements to 1000A.

The Model 514 is sized for a comfortable, one-handed operation. This model is average sensing and designed for traditional average responding electrical systems.

Features

  • Standard size, full function clamp-on meter
  • 1000AAC current measurements
  • 750VAC/1000VDC volt measurements
  • TRMS measurements
  • Resistance measurement to 4000Ω
  • Continuity with beeper below 40Ω
  • Frequency measurements from V and A
  • Diode test
  • 1ms Peak function for fast capture of signals
  • Hold function to "freeze" readings
  • Push-button for easy ADC zeroing
  • Large easy-to-read 4000-count display
  • 42-segment analog bargraph
  • Supplied with test leads and soft carrying case

Applications

  • Commercial, industrial, residential and HVAC troubleshooting
  • Power panel, junction box and battery bank monitoring
  • AC or DC motor testing
  • Power plant troubleshooting
  • Electrical testing and troubleshooting on non-linear loads, such as adjustable speed drives and computers

Electrical Specifications

AC Current

Range 0.05 to 1000Arms 
Resolution 40A: 0.01A; 400A: 0.1A; 1000A: 1A 
Basic Accuracy 50 to 60Hz: ±1.9% of Reading ± 5cts;
60 to 500Hz: ±2.5% of Reading + 5cts 
Frequency Range 50 to 500Hz 
Overload Protection 1200 Arms 

DC Amperes

Range 1A to 1000A 
Resolution 40A: 0.01A, 400A: 0.1A; 1000A: 1A 
Accuracy ±2.5% of Reading ± 10cts 
Overload Protection 1200 Arms 

AC Volts

Input Range 0.5V to 750V 
Resolution 400V: 0.1V / 750V: 1V 
Accuracy ±1.5% of Reading ± 5cts 
Input Impedance 10MΩ 
Overload Protection 1000Vrms 

Frequency

Input Current Input  Voltage Input 
Range 4kHz  10kHz  4kHz  10kHz 
Resolution 1Hz  10Hz  1Hz  10Hz 
Minimum Input Signal 2Arms  5Arms  5Vrms  10Vrms 
Accuracy ±0.1% of Reading ± 1ct
(20 to 10kHz) 
±0.1% of Reading ± 1ct
(10 to 10kHz) 

DC Volts

Range 0.2 to 1000V 
Resolution 400V: 0.1V; 1000V: 1V 
Accuracy ±1% of Reading ± 2cts 
Input Impedance 10MΩ 
Overload Protection 1000Vrms 

Continuity

Range Beeper 
Measurement <40Ω 
Max. Test Voltage 3VDC 
Overload Protection 600Vrms 

General Specifications

Digital Display: Digital: 3¾ digits LCD display, 4000-count (max. reading 3999)
Analog Display: Fast 42-segment analog bargraph display
Symbol & Scale Range: Automatic according to range and input signal
Polarity: Minus sign displayed when negative signal applied to input
Overload: OL Displayed when input signal exceeds range
Sample Rate: 2 samples/sec for the digital display; 20 samples/sec for the analog bargraph
Jaw Opening Size: 1.575" (40mm)
Battery: 9V, NEDA 1604 or 6F22 or 006P
Low Battery Indicator: Symbol displayed when the battery is below the required voltage
Auto Power Off: The meter will power itself OFF if there is no push button or rotary switch operation for 30 minutes
Dimensions: 9.53 x 2.60 x 1.42" (242 x 66 x 36mm)
Weight: 14.10oz (400g) with batteries

 Environmental Specification

Operating Temperature: 32° to 104°F (0° to 40°C), <80% RH, non-condensing
Storage Temperature: 14° to 140°F (-10° to 60°C), <70% RH, battery removed
Operating Altitude: 2167 ft (2000m)

Safety / Reference Specifications

Protection Level: Double insulation; EN 61010, 600V, Cat. III and EN 61010, 1000V, Cat. II
Agency Approvals: CE Mark