Ground resistance, harmonics, insulation
and transformer Testing

AEMC Products  AEMC Pricing

Digital Ground Resistance Tester Model 4610
Catalog# 2114.94

AEMC Model 4610
  • Fall of Potential method
  • Measures ground resistance (2-and  3-Point) and soil resistivity (4-Point)
  • Step voltage tests and touch potential measurements
  • Autoranging: Automatically selects the optimum range
  • Designed to reject high levels of noise and interference
  • Extremely simple to operate: connect- press- read
  • LED on face plate informs operator of high input noise, high auxiliary rod resistance and fault connections
  • Battery powered
  • Rugged dust proof and rain proof field case
  • Maybe used also for continuity tests on bonding
  • Color-coded terminals
  • CE Mark
AEMC Model 4610 Kit

4610 Kit 4-Point Ground Resistance Testers
Catalog# 2114.45

The Ground Resistance Tester Model 4610 is available alone or as a complete kit. The kit includes:

  • Meter
  • One 16 ft. color-coded lead
  • Two 100 ft. color-coded leads
  • Two 300 ft. color-coded leads on reels
  • Four auxiliary ground electrodes
  • Molded hard carrying case
  • Batteries
  • User manual

Description

Digital Ground Resistance Tester Model 4610 performs ground resistance and soil resistivity tests. Direct reading tester measures from 10 mW  to 1999W, and is autoranging, so it automatically seeks out the optimum measurement range. Easy to use - simply connect the leads, press to measure, and read.

The large LCD ( nearly 3/4" high) is easy to read, and also indicates low battery status, over range, and test lead shorts and lead reversals. Three LED indicators on the front panel continuously warn the user of measurement problems to ensure accurate and reliable tests.

The Model 4610 is fuse protected up to 250VAC to protect the instrument against voltage into the test leads.  In the event of a system fault, it can withstand 250VAC with spikes of 3000VAC or 1000VDC.

The heavy duty ABS case is O-ring sealed against dust and water, and the push-to-measure button is also sealed.  Model 4610 is battery powered, for convenient user in remote field applications.

Mechanical and Safety specifications, such as vibration and drop test, meet or
exceed IEC standards, to ensure safe and reliable field use.

 

Applications

The Ground Resistance Tester Model 4610 is a rugged, easy-to-use instrument ideal for maintenance crews performing numerous tests.The Model 4610 is designed to reject high levels of interference, so it can be used under difficult conditions  such as high stray currents that normally affect accuracy.

The Model 4610 may be used to perform the following tests:

  • Three Point measurements of resistance to ground of ground rods and grids. Three-Point measurements are generally used when the electrode or grid can be easily disconnected, if corrosion is suspected, or in circumstances where ground faults are unlikely to occur.
  • Four-Point tests or soil resistivity measurements .Locating areas of lowest soil resistivity is essential for achieving an economical grounding installation.
  • Touch potential measurements, an alternative to 3-point tests in evaluating electrical safety. This test is recommended  when the ground cannot be disconnected,  where ground faults are highly likely to occur, or when the "footprint" of grounded equipment (the outline of the part of equipment in contact with the earth) is comparable to the size of the ground to be tested.
  • Two-point tests for continuity tests on bonding or on pre-established grounds.  This test is commonly performed in urban environments where proper auxiliary electrode placement may be obscured by confined real estate.  Measurements are refernced against a good local ground conductor.

Specifications

ELECTRICAL

Measurement Ranges: 0 to 2000W

Measurement Range 0.00 to 19.99Ω  20.00 to 199.9Ω  200.0 to 1999Ω 
Ranges 20Ω  200Ω  2000Ω 
Resolution 10mΩ  100mΩ  1Ω 
Test Current 10mA  1mA  0.1mA 
Accuracy in % of Reading ±2% Reading ±1 ct  ±3% Reading ±3 cts 
Accuracy Reference Conditions 23°C ±3K, 50% RH ±10%, battery at 8V ±0.2V, externa; magnetic field <40A/m, external field <1 V/m, conductor centered, loop resistance noninductive. Accuracy % of reading 

Resistance Measurement Frequency:
128Hz square wave

Interference:
Model 4610 rejects high levels of interference voltage (DC, 50 to 60Hz, harmonics); DC voltage in series with X:20V AC voltage in series with Y:13V peak AC voltage in series with Z:32V peak

Response Time:
Approximately 6 seconds for a stabilized measurement

Voltage Withstand:
250VAC with spikes of 3000VAC or 1000VDC

Power Source:
Eight 1.5V "AA" batteries; Alkaline recommended;"LO BAT" indication on LCD

Battery Life:
1800 15-second measurements

Fuse Protection:
High breaking capacity 0.1A, 250V, 0.25" x 1.25"

Mechanical Specifications

Display: 7-segment LCD, .71" (18mm) high (3-1/2 digit); 2000 counts; LCD also indicates over range, test lead shorts and lead reversals
Connection: Color-coded terminals accept lugs with min. gap of 6mm or standard 4mm banana jacks
LED Indication: 3 LEDs indicate high input noise, high auxiliary rod resistance, open leads, blown fuse
Operating Temperature: 14° to 131°F (-10° to 55°C),0 to 90%RH
Storage Temperature: -40° to 158° F (-40° to 70° C), 0 to 90% RH with batteries removed
Dimensions: 8.7 x 5.4 x 5.9" (220 x 136 x 150mm)
Weight: 2.9 lbs. (1.3kg)
Case: Heavy-duty, ABS
Colors: Case: safety yellow; Front panel: gray
Mechanical Shock: IEC 68-2-27
Vibration Test: IEC 68-2-6
Drop Test: IEC 68-2-32
Dielectric Test: 3kV, 50/60Hz, 1 min. between four interconnected measuring terminals and any external metal ground
Environmental: O-ring sealed against dust and water to IP50 (Protection Index)
Electrostatic: IEC 801-2
Electromagnetic: IEC 801-3
Electric Shock: IEC 801-5

Safety / Reference Specifications

Safety Ratings: EN61010-1, Cat III, Pollution Degree 2, 42V